Finding Simultaneous Heating and Cooling Waste in a Building Twin

One of the quietest sources of wasted energy in a large building is simultaneous heating and cooling. A central air handler cools supply air to a low temperature. Then reheat coils in individual zones warm it again, because some rooms need less cooling than others. Both systems work correctly on their own, yet together they burn energy for nothing.

A building twin can make this visible. It links the 3D model of the building to live data: supply air temperature, valve positions on heating and cooling coils, damper positions, zone temperatures and setpoints. Because each sensor is tied to a room or an air handler, an engineer can ask a direct question: in which hours are the cooling coil and a reheat coil both open for the same air path?

A realistic case is an office floor in mild spring weather. The air handler keeps its cooling setpoint low all day to protect a few south-facing meeting rooms. The twin shows that for most of the morning, twelve other rooms on the floor are being reheated. Highlighting these rooms in the model lets the operator see the pattern in space as well as in time. The cause becomes clear: one fixed setpoint serves the worst room, not the average one.

The next step is to test a change before making it. The operator can raise the supply air setpoint in the twin and let a thermal model estimate what happens to room temperatures. If the south rooms would drift above their limit in the afternoon, the test shows it. The fix may then be a setpoint that resets with outdoor temperature, or a separate boost for those rooms only. The model supports the decision, but its results should be checked against measured data after the change.

Data quality matters here. A valve reading that sticks at ten percent open can look like leakage or like waste, depending on the case. Leaking valves, miscalibrated temperature sensors and manual overrides left on after maintenance are common false signals. Before trusting a finding, the team should confirm it on site with a quick inspection of the actuator or a reading from a handheld instrument.

Once a change is live, the twin keeps watching. A simple rule that flags any hour when both coils are open above a set threshold turns a one-time audit into routine monitoring. TwinUp builds digital twins for smart building management that bring this kind of sensor data into one model, so operators can find such waste without walking the plant room.

All posts

Frequently asked

What is simultaneous heating and cooling in a building?

Simultaneous heating and cooling happens when an HVAC system cools air and then reheats the same air at the same time. A central air handler may cool supply air to a low temperature while zone reheat coils warm it again. Each system works correctly alone, but together they waste energy.

Why does simultaneous heating and cooling happen?

A common cause is a fixed supply air setpoint that is set low to serve the hardest-to-cool room, such as a sunny meeting room. Other rooms then receive air that is colder than they need, so their reheat coils switch on. Stuck valves, bad sensors and manual overrides can also cause it.

What is a building digital twin?

A building digital twin is a real-time 3D replica of a building linked to live data from sensors and building systems. It ties readings such as air temperatures, valve positions and damper positions to specific rooms and equipment. Engineers can then inspect conditions and test changes in one model.

How does a building twin find simultaneous heating and cooling?

The twin compares zone data with plant behavior. It checks the hours when the cooling coil and a reheat coil are both open on the same air path. Because each sensor is linked to a room or air handler, the affected spaces can be highlighted in the 3D model and in time-based charts.

What data is needed to detect this kind of waste?

Useful data includes supply air temperature, valve positions on heating and cooling coils, damper positions, zone temperatures and zone setpoints. Each point must be mapped to the correct room or air handler. Outdoor temperature is also helpful when testing setpoint resets.

How can a twin help test a fix before it is applied?

An operator can raise the supply air setpoint in the twin and use a thermal model to estimate the effect on room temperatures. If certain rooms would exceed their limits, the test shows it in advance. The result guides whether to use an outdoor temperature reset or a separate boost for those rooms.

What are typical fixes for simultaneous heating and cooling?

Common fixes include a supply air setpoint that resets with outdoor temperature, or a dedicated boost for the few rooms with higher cooling needs. Repairing leaking valves, recalibrating sensors and removing leftover manual overrides also helps. The right fix depends on what the data and a site check show.

Why can the data give false signals?

Sensor and actuator faults can look like waste or hide it. A valve reading stuck at ten percent open may be leakage or genuine operation. Miscalibrated temperature sensors and overrides left on after maintenance are also common causes of misleading readings.

Should findings from the twin be verified on site?

Yes. Before acting on a finding, the team should confirm it with a quick inspection of the actuator or a reading from a handheld instrument. Model results should also be compared with measured data after any change is made.

Can the twin keep monitoring after the problem is fixed?

Yes. A simple rule can flag any hour when both coils are open above a set threshold. This turns a one-time energy audit into routine monitoring, so the problem is noticed if it returns.

Who benefits from this approach?

Facility managers, building operators and energy engineers in large offices and similar buildings benefit most. They can find hidden waste without walking through the plant room. Companies such as TwinUp build digital twins that bring this sensor data into one model.

How can a building team get started?

Start by listing which sensors and valve or damper signals the building management system already provides, and map them to rooms and air handlers. Then build a model that shows coil states and zone temperatures together. Begin with one air handler and one season, then expand.